Sale!

Watlow DC10-12P0-0000 DIN-A-MITE C SCR Power Controller

Product Model: DC10-12P0-0000
Product Brand: Watlow (DIN-A-MITE series)
Product Series / Platform: DIN-A-MITE C Solid State Power Controller

Product Features:

  • 55 A single-phase SCR controller, 100–120 VAC input/output, style C variant
  • Phase-angle (or optionally zero-cross) firing, with 4–20 mA input control
  • DIN-rail or panel / back-panel mounting; integrated heatsink; natural convection cooling
  • “Touch-safe” terminals, open-heater / shorted output alarm functionality

Description

Product Model: DC10-12P0-0000
Product Brand: Watlow (DIN-A-MITE series)
Product Series / Platform: DIN-A-MITE C Solid State Power Controller

Product Features:

  • 55 A single-phase SCR controller, 100–120 VAC input/output, style C variant
  • Phase-angle (or optionally zero-cross) firing, with 4–20 mA input control
  • DIN-rail or panel / back-panel mounting; integrated heatsink; natural convection cooling
  • “Touch-safe” terminals, open-heater / shorted output alarm functionality
DC10-12P0-0000
DC10-12P0-0000

Product Role & System Fit

The DC10-12P0-0000 is a solid state power control module in Watlow’s DIN-A-MITE C family. It functions as a replacement or upgrade to electromechanical contactors or mechanical relays in heater circuits, providing finer control over power delivery to resistive loads (e.g. heaters) by means of SCR (silicon controlled rectifier) switching.

Because of its compact design and versatility, it is well-suited for industrial heating systems, ovens, drying units, kilns, process heaters, and thermal control loops. As a DIN-rail or panel mount controller, it integrates readily into control panels or retrofit assemblies.

By using this controller instead of simple relay switching, you gain better control (phase-angle modulation, soft-start behavior, smoother power transitions) and improved longevity (no mechanical wear). In many control systems, DC10-12P0-0000 sits between a PID controller or PLC analog output (4–20 mA) and the heater load, converting the control signal to a high-current switching drive.

Technical Features & Benefits

High Current Capability
This variant handles 55 A in single-phase configuration at 100–120 VAC, making it suitable for medium to heavy heater loads.

Phase-Angle Firing with 4–20 mA Control Input
It supports phase-angle control (modulating the portion of each AC cycle passed to the load) based on a 4–20 mA input command. This gives fine-grain control of heater power.

Mounting Flexibility & Thermal Design
The DC10-12P0-0000 can mount on a standard DIN-rail or use back-panel mounting, with integrated heat sink and natural convection cooling design (no forced fans required).

Safety Features & Diagnostics
It includes touch-safe (insulated) terminals, and open heater / shorted output alarm signals, which help detect load failures or wiring faults.

Compact & Rugged Construction
As part of the DIN-A-MITE C family, it is designed for industrial use with rugged construction, high short-circuit current ratings (SCCR), and a compact footprint.

Technical Specifications

Specification Value / Description
Model / Part Number DC10-12P0-0000
Product Family Watlow DIN-A-MITE C
Configuration / Style Style C (single-phase, one controlled leg)
Line / Load Voltage 100–120 VAC (single-phase)
Current Rating 55 A continuous (at 50 °C ambient)
Control Input 4–20 mA (for phase-angle control)
Output Firing Mode Phase-angle (also selectable zero-cross in some variants)
Mounting Options DIN-rail (EN 50022) or panel / back-panel mount
Cooling Method Natural convection via heatsink (no fan)
Alarm / Diagnostic Feature Open heater / shorted output alarm option
Short-Circuit Rating 200 kA SCCR (with proper fusing, per DIN-A-MITE specs)
Input / Output Phases Supported 1-phase (style C) ; other DIN-A-MITE variants support three-phase modes
Ambient / Thermal Specification Ambient up to ~80 °C per family spec; Style C variant rated for typical industrial ranges

Installation & Maintenance Insights

Here are practical tips when deploying or servicing DC10-12P0-0000:

  • Mounting & Clearance
    Ensure sufficient clearance around the heatsink and airflow path. Avoid placing it adjacent to heat sources. Use DIN-rail or panel mount, as appropriate.
  • Wiring Practices
    Use correctly sized conductors for the output (load) current. Keep control wiring (4–20 mA) separate from power wiring to reduce interference.
  • Fuse / Protection Coordination
    Provide appropriate upstream overcurrent protection (fuses or breakers) sized per the heater and the controller’s capabilities. Ensure the SCCR rating is not exceeded.
  • Control Signal Scaling
    Calibrate the 4–20 mA input to map to 0–100 % firing output. Test full and zero extremes.
  • Diagnosis & Alarm Test
    Simulate open-heater or short-circuit conditions to verify alarm capability. Monitor that alarms trigger as expected.
  • Thermal Monitoring
    Periodically check that the controller’s heatsink remains within acceptable temperature during high-load operations.
  • Replacement / Spare Strategy
    Keep at least one spare controller of the same model (DC10-12P0-0000) and ensure firmware / configuration compatibility.
  • Cleaning & Visual Inspection
    Clean dust from fins or heatsink, inspect terminals for corrosion, check tightness of wiring connections.