Sale!

IC200ALG430C GE  Analog I/O Module – High Isolation, 4 In/2 Out

Product Model: IC200ALG430C
Product Brand: GE Fanuc / Emerson Automation Solutions
Product Series: VersaMax Analog Mixed I/O Module

Key Features:

  • Mixed analog I/O: four current input channels (4‑20 mA) + two current output channels (4‑20 mA) in one module.
  • 12‑bit resolution (≈4 µA / 8 counts on inputs) for precise measurement and control.
  • High isolation: user input to logic/frame ground rated ~250 VAC continuous and 1500 VAC for one minute (in many specs) for industrial robustness.
  • Compact footprint, single slot module in VersaMax rack, ideal when panel space is limited and you need both inputs and outputs.
Categories: , , , , Brand:

Description

Product Model: IC200ALG430C
Product Brand: GE Fanuc / Emerson Automation Solutions
Product Series: VersaMax Analog Mixed I/O Module

Key Features:

  • Mixed analog I/O: four current input channels (4‑20 mA) + two current output channels (4‑20 mA) in one module.
  • 12‑bit resolution (≈4 µA / 8 counts on inputs) for precise measurement and control.
  • High isolation: user input to logic/frame ground rated ~250 VAC continuous and 1500 VAC for one minute (in many specs) for industrial robustness.
  • Compact footprint, single slot module in VersaMax rack, ideal when panel space is limited and you need both inputs and outputs.
IC200CPUE05
IC200ALG430C
Specification Description
Model Number IC200ALG430C
Brand GE Fanuc / Emerson Automation Solutions
Series VersaMax Analog Mixed I/O Module – 12‑bit resolution
Number of Channels 4 differential analog input channels + 2 single‑ended analog output channels
Input Signal Range 4‑20 mA (current loops) for input channels
Output Signal Range 4‑20 mA (current) for output channels
Resolution 12‑bit (≈4 µA input resolution)
Update Rate Input ~0.4 ms; Output ~0.3 ms
Input Filter Response 5.0 ms typical
Isolation (User Input to Logic/Frame) 250 VAC continuous; 1500 VAC for 1 minute
Input Impedance Max ~200 Ω (for current input)
Backplane Current Draw 50 mA @ 5 V DC max
External Power Supply (Field Side) +18 to +30 V DC recommended; 9.6‑15 V DC nominal for some circuits
Accuracy ±0.3% typ of full scale @25 °C; ±0.5% max @25 °C; ±1% max @0‑60 °C
Module Mapping 4 words analog input data, 2 words analog output data