Sale!

GE IC695ALG112 RX3i 12‑Channel Isolated Analog Input Module

Product Model: GE IC695ALG112
Product Brand: GE Fanuc (now GE/Emerson PACSystems)
Product Series: RX3i / PACSystems Analog Input Modules

Product Features:
• 12 fully‑isolated analog input channels, configurable for either voltage or current ranges.
• Supports a wide variety of ranges: voltage (±10 V, 0–10 V, ±5 V, 0–5 V, 1–5 V) and current (0–20 mA, 4–20 mA, ±20 mA) without jumpers.
• Single‑slot installation in RX3i universal backplane with comprehensive diagnostics (open‑wire detection, over‑range detection).
• High resolution A/D conversion (16‑bit representation), strong noise immunity, solid data quality for demanding analog loops.

Categories: , , , , Brand:

Description

Product Model: GE IC695ALG112
Product Brand: GE Fanuc (now GE/Emerson PACSystems)
Product Series: RX3i / PACSystems Analog Input Modules

Product Features:
• 12 fully‑isolated analog input channels, configurable for either voltage or current ranges.
• Supports a wide variety of ranges: voltage (±10 V, 0–10 V, ±5 V, 0–5 V, 1–5 V) and current (0–20 mA, 4–20 mA, ±20 mA) without jumpers.
• Single‑slot installation in RX3i universal backplane with comprehensive diagnostics (open‑wire detection, over‑range detection).
• High resolution A/D conversion (16‑bit representation), strong noise immunity, solid data quality for demanding analog loops.

IC695CRU320-EZ
IC695ALG112
IC695CRU320-EZ
IC695ALG112
Specification Description
Model GE IC695ALG112
Brand GE Fanuc / Emerson PACSystems
Series RX3i – Analog Input Module
Module Type Isolated Analog Input Module – 12 channels
Input Channels 12 isolated channels
Supported Voltage Ranges ±10 V, 0–10 V, ±5 V, 0–5 V, 1–5 V
Supported Current Ranges ±20 mA, 0–20 mA, 4–20 mA
Slot Requirement 1 slot in RX3i universal backplane
Internal Power Draw Approx. 490 mA at +5 V; ~310 mA at +3.3 V (typical values)
Max Power Dissipation ~4.89 W maximum (all 12 channels @ 20 mA)
Digital Filter Options 8 Hz, 12 Hz, 16 Hz, 40 Hz, 250 Hz, 1000 Hz
Response Time <1.7 ms settling for step input (analog front‑end)
Isolation Terminal block to backplane: 250 VAC continuous, 1500 VAC for 1 minute
Accuracy 0.1 % of span at 25 °C; 0.2 % over full temperature range
Compatible Termination High‑capacity terminal block often required (per vendor note)
Recommended CPU Firmware RX3i CPU firmware v5.0 or later